Clearing old electrics for the plumbers, then a fault-find, at a Hampstead office.
We stripped out redundant services so a law firm’s plumbing work could go ahead, then came back to trace sockets that were tripping the board.

A law firm’s office in Hampstead was having plumbing work done and needed redundant electrics cleared out of the way first. On a return visit, some sockets were tripping the board.
At a glance
| Location | Hampstead, Camden (NW3) |
|---|---|
| Completed | March 2026 |
| Work | Office electrical works and fault-finding |
| Property | Law firm’s office |
| Time on site | Two visits (25 Feb and 19 Mar 2026) |
| SEG team | Matthew |








What we found
- Redundant services in a cupboard: an old alarm and its switch, a double socket and the switch for a water heater
- A 6mm² supply on a 32A breaker that fed the old water heater
- On the return visit: an insulation resistance fault between the board and the first socket on the tripping circuit
- The board’s RCD main switch failed its test
What we did
- First visit: removed the redundant alarm, switches and socket, took the water heater supply out of the board and made all the dead cables safe, ready for the plumbers
- Return visit: refitted the cupboard cut-outs and removed power that was no longer needed there
- Tested the tripping circuit, disconnected the faulty section and made it safe
- Replaced a grommet strip in the board with a fire-sealed grommet
- Checked all the other circuits were working correctly
- Recommended a new board with RCBOs, so each circuit has its own protection, and a short run of trunking to re-feed the socket that lost power
Equipment used
- Kewtech KT63DL multifunction tester
Need something similar in Hampstead? See commercial electrical work in London and commercial electrical maintenance, or electricians near Hampstead. Call 01727 238 999 or tell us about the job.
More recent local jobs
- Lighting, power, data, fire alarm and door entry for serviced apartments at 37 Doughty Street, Bloomsbury, London, 2022
- Cisco Wi-Fi, Verkada access control and AV for James Hambro's new Edinburgh office, Edinburgh, October 2026 (in progress)
- LD1 Aico smoke alarms for a sheltered housing scheme in Walthamstow, Walthamstow, October 2026 (in progress)
- Garden uplights and floodlights traced and fixed over two visits, Totteridge, September 2026
From SEG’s job records and engineers’ photos. Customer details are kept private.
Need it done by a date?
Tell us the deadline. We’ll tell you honestly whether we can hit it — and we usually can.