A solar PV system that kept tripping the RCD in London Colney.

The inverter was off and the house RCD kept tripping. Testing pinned it down, and the inverter maker confirmed the fix: its own 100mA RCD.

Solis inverter with AC and DC isolators in the loft

A tenant's solar PV system kept tripping the house RCD and the inverter was off. SEG investigated and re-arranged the PV circuit protection to the inverter maker's requirements.

At a glance
LocationLondon Colney (AL2)
CompletedMarch 2026
WorkSolar PV fault-finding
PropertySemi-detached house
Time on siteTwo visits (26 Feb and 6 Mar 2026)
SEG teamTom and Matthew
Solis inverter with AC and DC isolators in the loft
Solis inverter with AC and DC isolators in the loft
New 100mA RCD enclosure for the PV above the consumer unit
New 100mA RCD enclosure for the PV above the consumer unit
Solar PV schematic displayed beside the inverter
Solar PV schematic displayed beside the inverter
Hager consumer unit after the PV circuit was rearranged
Hager consumer unit after the PV circuit was rearranged
Clamp meter test on the PV isolator during fault-finding
Clamp meter test on the PV isolator during fault-finding

What we found

  • Inverter off and the PV MCB off on arrival
  • AC side insulation resistance clear up to the inverter isolator; DC strings (front and rear roof, in series) tested clear to earth
  • Insulation resistance dropped significantly when the inverter AC isolator was on, and cleared with the PV neutral disconnected
  • Inverter manufacturer advised against 30mA RCD protection (the inverter has its own RCD) and recommended a dedicated 100mA RCD
  • Damaged bird mesh on the array

What we did

  • Fault-found on the Solis inverter, AC/DC isolators and strings in the loft
  • Tightened terminals in the DC isolator and checked all AC isolator connections
  • Spoke to the inverter manufacturer's technical team to confirm the correct protection
  • Moved the PV MCB to before the RCDs in the Hager board
  • Fitted a secondary enclosure with a 2-pole 100mA Type A bi-directional, non-time-delayed RCD and 20A Hager MCB for the PV
  • Tested Ze, PFC and R1+R2 for the PV circuit at the inverter isolator
  • Relabelled the main board and labelled the new enclosure; all left working

Equipment used

  • Solis S5 series inverter
  • Hager consumer unit (existing)
  • 100mA Type A 2-pole bi-directional RCD
  • Hager 20A MCB
Need something similar in London Colney? See solar PV, or electricians in London Colney. Call 01727 238 999 or tell us about the job.

More recent local jobs

From SEG’s job records and engineers’ photos. Customer details are kept private.

Re-roofing with solar panels on the roof? Solar panel removal and reinstall

Need it done by a date?

Tell us the deadline. We’ll tell you honestly whether we can hit it — and we usually can.

Contact

Talk to SEG

Questions about a job, a certificate or a programme of works? Call the office or send a message. Head office in St Albans, serving Herts, Beds, Bucks and London.

Emailhello@segplc.comPhone01727 238 999Also on0345 3 822 833OfficeSEG House, 192 Watford Road, Chiswell Green, St Albans, Herts AL2 3EBHours7 days, 7am–10pm · call-outs every dayLeadershipMichael Simm · Russell Solts
Call nowGet a quote