Checking another installer’s extension wiring in Chiswell Green.

Homeowners were worried about the electrics in their new kitchen extension. We audited the work, carried out an EICR and made the urgent faults safe on the spot.

Dual-RCD consumer unit inspected and relabelled during the EICR

Homeowners were worried about electrical work in their new kitchen extension carried out by another installer. SEG audited the work and carried out an EICR, putting right the most urgent faults on the spot.

At a glance
LocationChiswell Green (AL2)
CompletedJuly 2026
WorkEICR and remedials
PropertyFamily home with a new extension
Time on siteAudit (23 Jun 2026) then EICR visit (10 Jul 2026)
SEG teamJamie and Matthew
Dual-RCD consumer unit inspected and relabelled during the EICR
Dual-RCD consumer unit inspected and relabelled during the EICR
RCD test showing a pass during the extension EICR
RCD test showing a pass during the extension EICR
Kitchen appliance grid switch re-terminated after loose connections found
Kitchen appliance grid switch re-terminated after loose connections found
Inside the consumer unit during inspection and testing
Inside the consumer unit during inspection and testing
LED floor light found without an earth continuity conductor
LED floor light found without an earth continuity conductor
Before: cracked double socket, replaced during the inspection
Before: cracked double socket, replaced during the inspection

What we found

  • Exposed single insulation and loose connectors under kitchen base units; one cable with no connector at all
  • Twin and earth laid in the floor screed with no mechanical protection
  • LED floor lights with bare cables and no circuit protective conductor continued to metal fittings
  • Earths twisted together unsleeved in the appliance grid switch; oven cable came out of its terminal
  • Loose neutrals and damaged cables on the ground-floor sockets; a broken double socket
  • Board incorrectly labelled; the previous EIC ticked board replacement but recorded only 3 circuits and listed Type AC RCDs where Type A were fitted

What we did

  • Visual audit of the extension works with a written list of concerns
  • Full EICR of the installation
  • Re-terminated the kitchen appliance grid switch
  • Dropped and re-made ground-floor sockets to cure loose neutrals and restore continuity
  • Replaced the damaged double socket
  • Made bare cables safe under the units
  • Tested both Type A RCDs (pass)
  • Relabelled the consumer unit correctly

Equipment used

  • Kewtech KT63DL tester

Paperwork: EICR.

Need something similar in Chiswell Green? See EICR testing, or electricians in Chiswell Green. Call 01727 238 999 or tell us about the job.

More recent local jobs

From SEG’s job records and engineers’ photos. Customer details are kept private.

Need it done by a date?

Tell us the deadline. We’ll tell you honestly whether we can hit it — and we usually can.

Contact

Talk to SEG

Questions about a job, a certificate or a programme of works? Call the office or send a message. Head office in St Albans, serving Herts, Beds, Bucks and London.

Emailhello@segplc.comPhone01727 238 999Also on0345 3 822 833OfficeSEG House, 192 Watford Road, Chiswell Green, St Albans, Herts AL2 3EBHours7 days, 7am–10pm · emergencies by arrangementLeadershipMichael Simm · Russell Solts
Call nowGet a quote