Three days of EICR remedial work in Hertford.
An older town-centre property, a list of defects from its EICR, and three boards to replace. Everything put right, tested and labelled.

An EICR on an older town-centre property listed a range of defects. The owner instructed SEG to carry out the remedial works, including the boards serving the house, utility room and garden outbuilding.
At a glance
| Location | Hertford (SG14) |
|---|---|
| Completed | June 2026 |
| Work | EICR remedial works |
| Property | Older town-centre property with garden outbuilding |
| Time on site | Three days (28-29 May and 1 Jun 2026) |
| SEG team | Tom, Henry, George and Arthur |






What we found
- Downlights joined with connector blocks, with exposed conductor whiskers
- Socket back box not secured (missing lug) and a broken socket
- Twin and earth clipped externally with no mechanical or UV protection
- Poor end-to-end readings on a ring final circuit caused by loose terminations
- Damaged PIR on the rear external light
What we did
- Replaced the main distribution board, building a spacer to bridge two wall depths, and relocated the main earthing terminal
- Installed a 2-pole isolation switch and used the old enclosure as an isolated joint box
- Replaced the utility-room and outbuilding boards (Wylex), fitting banjos and crimped fly leads to the SWA glands for sound earths
- Re-terminated every downlight with Wago connectors in safe enclosures and replaced bathroom downlights with IP-rated units
- Replaced damaged sockets and repositioned an external socket to keep water out
- Fitted new shed lights and external lanterns
- Ran new conduit discreetly behind the guttering to protect the external cable
- Split the ring, found and tightened loose terminations, and retested to good readings
- Torqued all terminals, tested RCDs, polarity and earth fault loop at all points, and labelled all boards
Equipment used
- Wylex consumer units / distribution boards
- Wylex RCBOs
- Wago connectors
- IP-rated downlights
- External lanterns
Need something similar in Hertford? See EICR testing and consumer unit replacement, or our work across Hertfordshire. Call 01727 238 999 or tell us about the job.
More recent local jobs
- 85-inch screens wall-mounted and a new network switch for Master Mix, Frogmore, November 2026
- Lighting, power, data, fire alarm and door entry for serviced apartments at 37 Doughty Street, Bloomsbury, London, 2022
- Cisco Wi-Fi, Verkada access control and AV for James Hambro's new Edinburgh office, Edinburgh, October 2026 (in progress)
- LD1 Aico smoke alarms for a sheltered housing scheme in Walthamstow, Walthamstow, October 2026 (in progress)
From SEG’s job records and engineers’ photos. Customer details are kept private.
Need it done by a date?
Tell us the deadline. We’ll tell you honestly whether we can hit it — and we usually can.