  2. Storage heater not working

Storage heater not working?

What to check first, the faults we find most often, and when to call an electrician.

Digital control panel on a new storage heater

A storage heater that is cold when you need it is usually one of a handful of things, and several of them you can check yourself in five minutes. We go out to storage heater faults every winter, including more than 130 call-outs in retirement and sheltered flats since July 2025. Below is what to check first, what we find most often, and when to call us.

Burning smell, scorch marks or black marks on the wall? Switch the heater off at the switch on the wall and do not use it. Then call us.

Quick checks before you call

  1. Is it switched on at the wall? Most storage heaters have a switch or fused spur next to them, and newer ones have two: one for the off-peak (night) supply and one for the 24-hour supply. Both need to be on.
  2. Is the input (charge) turned up? The input dial sets how much heat it stores overnight. On zero or 1 it will be cold the next day. In cold weather it needs to be high.
  3. Is the output turned down overnight? The output dial (or damper) lets the stored heat out. If it is left open all night, the heat has gone by the morning.
  4. Has the clock or programme reset? Newer heaters with digital controls have a clock and a weekly programme. A power cut can reset them, so the heater charges at the wrong time.
  5. Has a breaker tripped? Look at the fuse board for the storage heater circuits. On many homes these are on a separate board or a separate part of the board, next to a second meter or a dual-rate meter.
  6. Is anything covering it? Clothes, a sofa or a curtain over the grille stops the heat getting out and can trip the safety cut-out.

What we find most often

From our engineers’ notes on more than 130 storage heater call-outs in retirement and sheltered flats (July 2025 to September 2026):

  • The heater was worn out. This was the most common finding: the heater needed replacing. Old heaters lose their insulation and their controls stop working, and parts are hard to get.
  • The settings, timer or programme were wrong on at least 23 visits. The heater was fine; it was simply not set to charge enough, or at the right time.
  • It had been switched off at the wall, the spur or the breaker on at least 10 visits.
  • A switch, spur or connection had failed on at least 11 visits: a worn 20A switch, a loose conductor, water in a back box, a cable fixed on its insulation.
  • The supply was wrong on at least 4 visits: a newer heater that needs both an off-peak and a 24-hour supply had only one.
  • The thermostat was stuck, so the heater got very hot and could not be turned down, on at least 3 visits.

So before anything is replaced, it is worth checking the simple things. We do that first on every call-out.

Common causes, and what they look like

  • Cold all day, cold to touch in the morning: it is not charging. Check the off-peak switch and breaker, then the off-peak supply itself (below). If power is reaching the heater, the element, the input thermostat or the thermal cut-out has failed.
  • Warm in the morning, cold by the afternoon: it is charging but losing the heat too early. Turn the output down overnight and the input up. If that makes no difference, the output damper or its thermostat may have failed, or the insulation has worn out on an old heater.
  • Too hot all the time and it will not turn down: the input thermostat is likely stuck. Switch it off at the wall and call us.
  • Keeps tripping the breaker: a loose connection, a failed switch or spur, or a fault in the heater. This needs testing, not resetting.
  • One heater out of several not working: usually that heater, its switch or its connection rather than the supply.
  • All the storage heaters stopped at once: usually the off-peak supply, the off-peak breaker or the time switch, not the heaters.

The thermal cut-out

Storage heaters have a thermal cut-out, a safety device that switches the elements off if the heater gets too hot. It usually trips because the grille has been covered, or because a thermostat has failed. On some models it resets itself once the heater cools down; on others it has to be reset or replaced by an engineer, behind the front panel. Please do not take the casing off yourself: the bricks hold a lot of heat and the elements are live. If the cut-out trips again after it has been reset, the cause needs finding.

When the off-peak supply is the problem

Storage heaters charge on a cheaper night-time supply (Economy 7 or a similar tariff), switched on by a time switch at the meter. If none of your storage heaters charge, check the off-peak breaker first, then whether the meter’s night rate is coming on. Many homes had their off-peak switched by a radio signal (the Radio Teleswitch), which has now been switched off; if your meter has not been replaced, your heaters may be charging at the wrong times or not at all. Your energy supplier replaces the meter, and we check the wiring and the heaters. See Economy 7 and the Radio Teleswitch switch-off.

Real call-outs from this winter and last

  • Heater on two off-peak supplies (Enfield, EN1, January 2026): a newer heater needs a 24-hour supply for its controls, but both spurs were fed from the off-peak. We extended the ring to add a 24-hour supply and renewed both spurs.
  • Breaker kept tripping (Enfield, EN3, January 2026): a loose conductor at the heater’s switch. Made good, the heater worked and the breaker stopped tripping.
  • No power at the heater (Cambridge, CB1, August 2025): in the spur, the cable to the heater had been fixed on its insulation, so the live conductor was not connected. Reconnected and tested.
  • Heater stopped after damp weather (Hendon, NW4, November 2025): water trapped in the back box behind the spur. Dried out, checked and working.
  • Cold every afternoon (Hemel Hempstead, HP1, October 2025): the heater’s time clock had been changed and was not allowing it long enough to charge. Reset.
  • Too hot and would not turn down (Milton Keynes, MK6, November 2025): the thermostat had failed. The heater was replaced.
  • Heaters past repair (Hazlemere, HP15, and Milton Keynes, MK6, spring 2026): old heaters that no longer held their heat, replaced with new Elnur storage heaters and their flex connections renewed.

From our repair work in retirement and sheltered housing across Buckinghamshire, Bedfordshire, Hertfordshire and London. No residents or addresses named.

Repair or replace?

If the heater is less than about 15 years old and the fault is a switch, a connection, a thermostat or the settings, a repair is usually worth it. If it is older, has damaged insulation or needs a part that is no longer made, replacing it with a modern heater with built-in controls is often the better spend. See storage heater repairs and replacement. Housing providers: see responsive repairs.

Storage heater still cold after these checks? Call 01727 238 999 or tell us the make and what it is doing. A photo of the label and the switches on the wall helps.

Questions we’re asked

Why is my storage heater cold?

Usually because it has not charged overnight: it is switched off at the wall, the input is turned down, the clock or programme has reset, the off-peak breaker has tripped, or the off-peak supply is not coming on. If all of those are fine and it is still cold, the element, thermostat or thermal cut-out may have failed.

Why is my storage heater cold by the afternoon?

The stored heat is being let out too early. Turn the output down overnight and the input up, especially in cold weather. If it still runs out, the output damper or its thermostat may have failed, or an old heater has lost its insulation.

Where is the reset button on a storage heater?

Many storage heaters have a thermal cut-out behind the front panel rather than a button you can reach. Some reset themselves once cool. Do not remove the casing yourself: the bricks are hot and the elements are live. If it keeps tripping, there is a cause to find.

Why is my storage heater too hot and will not turn down?

The input thermostat is probably stuck. Switch the heater off at the wall and have it checked. On our call-outs a stuck thermostat usually meant the heater needed replacing.

All my storage heaters stopped working at once. Why?

That points to the supply rather than the heaters: the off-peak breaker, the time switch, or the off-peak rate not coming on at the meter. Since the Radio Teleswitch was switched off, some older meters no longer switch the off-peak supply correctly.

Do you repair storage heaters for landlords and housing providers?

Yes. We have attended more than 130 storage heater call-outs in retirement and sheltered flats since July 2025, and we work for private landlords too.

Written by SEGplc. Last updated 13 November 2026.

Need it done by a date?

Tell us the deadline. We’ll tell you honestly whether we can hit it — and we usually can.

Contact

Talk to SEG

Questions about a job, a certificate or a programme of works? Call the office or send a message. Head office in St Albans, serving Herts, Beds, Bucks and London.

Emailhello@segplc.comPhone01727 238 999Also on0345 3 822 833OfficeSEG House, 192 Watford Road, Chiswell Green, St Albans, Herts AL2 3EBHours7 days, 7am–10pm · call-outs every dayLeadershipMichael Simm · Russell Solts
Call nowGet a quote